MDR-20
Name: MDR-20
Product catalog: Din rail power supply (DR and MDR)

Print this Page        Skype Online

E-mail Us                QQ

Whatsapp               wangwang

Facebook                Youtube

Wechat
20W Single Output Industrial DIN Rail Power Supply   MDR-20 series
Features:
Universal AC input/ full range 
Protections: Short circuit/ Over load/ Over voltage 
Cooling by free air convection 
Can be installed on DIN rail TS-35/7.5 or 15  
LED indicator for power on
100% full load burn-in test 
2 years warranty
SPECIFICATIONS  
OUTPUT  
Model MDR-20-5 MDR-20-12 MDR-20-15 MDR-20-24
DC Voltage  5V 12V 15V 24V
Rated Current  3A 1.67A 1.34A 1A
Current Range  0-3A 0-1.67A 0-1.34A 0-1A
Rated Power  15W 20W 20W 24W
Ripple & Noise  80mVp-p 120mVp-p 120mVp-p 150mVp-p
Voltage Tolerance  ±2% ±1% ±1% ±1%
Line regulation  ±1.0% ±1.0% ±1.0% ±1.0%
Load regulation ±1.0% ±1.0% ±1.0% ±1.0%
Setup, Rise Time  500ms,30ms/230VAC   1000ms,30ms/115VAC at full load
Hold Up Time  50ms/230VAC   25ms/115VAC at full load
   
INPUT  
Voltage Range  85~264VAC   47~63Hz; 120~370VDC
AC Current 0.55A/115VAC   0.35A/ 230VAC
Efficiency 76% 80% 81% 84%
Inrush Current  Cold start 20A/115V   40A/230V
Leakage Current <1mA/240VAC
   
PROTECTION  
Over Load  105% ~ 160% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage  5.75-6.75V 13.8-16.2V 17.25-20.25V 27.6-32.4V
Protection type: Shut down o/p voltage, re-power on to recover
   
ENVIRONMENT  
Working Temp., Humidity -20℃~+70℃; 20%~90% RH non-condensing
Storage Temp., Humidity -40℃~+85℃; 10%~95%RH
Temp. Coefficient ±0.03%/℃(0~50℃)
Vibration 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes
   
SAFETY  
Withstand Voltage I/P-O/P: 3KVAC   I/P-FG:2KVAC   O/P-FG:0.5KVAC
Isolation Resistance I/P-O/P, I/P-FG, O/P-F/G: 100M Ohms / 500VDC/25℃/70% RH
   
STANDARD  
Safety Standard Design refer to UL508,TUV EN60950-1
EMC Standard Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-1,EN61204-3, light industry level, criteria A
   
OTHERS  
Dimension 22.5*90*100mm(W*H*D)
Weight 0.19Kg
Packing 72pcs/carton/14.7kg/0.91CUFT
   
NOTE  
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor. 
3.Tolerance: includes set up tolerance, line regulation and load regulation.
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

If you have any enquiry about quotation or cooperation , please feel free to email us at Leyu@leyuelec.com or use the following enquiry form . Our sales representative will contact you within 24 hours. Thank you for your interest in our products.