75W Single Output Industrial DIN Rail Power Supply   DR-75 series
Features:
Universal AC input/ full range 
Protections: Short circuit/ Over load/ Over voltage/ Over temperature
Cooling by free air convection 
Can be installed on DIN rail TS-35/7.5 or 15 
LED indicator for power on 
100% full load burn-in test 
Fixed switching frequency at 50KHz 
2 years warranty
 
SPECIFICATIONS  
OUTPUT  
Model DR-75-12 DR-75-24 DR-75-48
DC Voltage  12V 24V 48V
Rated Current  6.3A 3.2A 1.6A
Current Range  0-6.3A 0-3.2A 0-1.6A
Rated Power  75.6W 76.8W 76.8W
Ripple & Noise  100mVp-p 150mVp-p 240mVp-p
Voltage Adj. Range  12-14V 24-28V 48-53V
Voltage Tolerance  ±2% ±1% ±1%
Line regulation ±1% ±1% ±1%
Load regulation ±1% ±1% ±1%
Setup, Rise Time  1000ms,60ms/230VAC   1800ms,60ms/115VAC at full load
Hold Up Time  60ms/230VAC   12ms/115VAC at full load
   
INPUT  
Voltage Range  85~264VAC   47~63 Hz; 120~370VDC
AC Current 1.6A/115V   0.96A/230V
Efficiency 76% 80% 81%
Inrush Current  Cold start 20A/115VAC   40A/230VAC
Leakage Current <1mA/240VAC
   
PROTECTION  
Over Load  105%~150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage  15-16.5V 29-34V 58-65V
Protection type: Shut down o/p voltage, re-power on to recover
Over Temp. 85℃±5℃ (TSW1) detect on heat sink of power transistor
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
   
ENVIRONMENT  
Working Temp., Humidity -10℃~+60℃; 20%~90% RH non-condensing
Storage Temp., Humidity -20℃~+85℃; 10%~95%RH
Vibration 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes
   
SAFETY  
Withstand Voltage I/P-O/P: 3KVAC   I/P-FG: 1.5KVAC   O/P-FG: 0.5KVAC
Isolation Resistance I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC/25℃/70%RH
   
STANDARD  
Safety Standard Design refer to UL508,TUV EN60950-1 
EMC Standard EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2, heavy industry level, criteria A
   
OTHERS  
Dimension 55.5*125.2*100mm(L*W*H)
Weight 0.6Kg
Packing 20pcs/13Kg/1.29CUFT
   
NOTE  
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor. 
3.Tolerance: includes set up tolerance, line regulation and load regulation.
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

If you have any enquiry about quotation or cooperation , please feel free to email us at Leyu@leyuelec.com or use the following enquiry form . Our sales representative will contact you within 24 hours. Thank you for your interest in our products.