60W Single Output DIN Rail Power Supply   MDR-60 series
Features:
Universal AC input/ full range
Protections: Short circuit/ Over load/ Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
isolation classⅡ
LED indicator for power on
100% full load burn-in test
2 years warranty


SPECIFICATIONS  
OUTPUT  
Model MDR-60-5 MDR-60-12 MDR-60-24 MDR-60-48
DC Voltage  5V 12V 24V 48V
Rated Current  10A 5A 2.5A 1.25A
Current Range  0-10A 0-5A 0-2.5A 0-1.25A
Rated Power  50W 60W 60W 60W
Ripple & Noise  80mVp-p 120mVp-p 150mVp-p 200mVp-p
Voltage Tolerance  ±2% ±1% ±1% ±1%
Line regulation  ±1.0% ±1.0% ±1.0% ±1.0%
Load regulation ±1.0% ±1.0% ±1.0% ±1.0%
Setup, Rise Time  500ms,30ms/230VAC   200ms,30ms/115VAC at full load
Hold Up Time  50ms/230VAC   20ms/115VAC at full load
   
INPUT  
Voltage Range  85~264VAC   47~63Hz; 120~370VDC
AC Current 1.8A/115VAC   1A/ 230VAC
Efficiency 78% 86% 88% 87%
Inrush Current  Cold start 30A/115VAC   60A/230VAC
Leakage Current <1mA/240VAC
   
PROTECTION  
Over Load  105%~150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage  6.25-7.25V 15.6-18V 31.2-36V 57.6-64.8V
Protection type: Shut down o/p voltage, re-power on to recover
   
ENVIRONMENT  
Working Temp., Humidity -20℃~+70℃; 20%~90% RH non-condensing
Storage Temp., Humidity -40℃~+85℃; 10%~95%RH
Temp. Coefficient ±0.03%/℃(0~50℃)
Vibration 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes
   
SAFETY  
Withstand Voltage I/P-O/P: 3KVAC   I/P-FG:2KVAC   O/P-FG:0.5KVAC
Isolation Resistance I/P-O/P, I/P-FG, O/P-F/G: >100M Ohms / 500VDC/25℃/70% RH
   
STANDARD  
Safety Standard Design refer to UL508, UL60950-1,TUV EN60950-1,EN50178 
EMC Standard Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2,EN61204-3, heavy industry level, criteria A
   
OTHERS  
Dimension 40*90*100mm(W*H*D)
Weight 0.33Kg
Packing 42pcs/carton/14.8kg/0.82CUFT
   
NOTE  
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor.
3.Tolerance: includes set up tolerance, line regulation and load regulation.
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.